EasyManua.ls Logo

Siemens SINUMERIK 804D sl

Siemens SINUMERIK 804D sl
319 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tips
13.4 Integrating PG/PC into the network (NetPro)
CNC Part 1 (NCK, PLC, drive)
Commissioning Manual, 11/2006, 6FC5397-2AP10-2BA0
193
13.4.1 Integrating PG/PC into NetPro
Introduction
To enable the communication between PG/PC <-> HMI via Ethernet, the PC/PG is to be
included in the network configuration of the system.
To integrate the PG/PC, proceed from the following starting situation in the
SIMATIC Manager.
You are in the HW config in the created project "PLC-Erst-IBN 840D sl" (see figure below).
&KRRVH1HW3UR
Figure 13-7 HW config project "PLC-Erst-IBN 840D sl"
Operator input sequence steps - Integrating PG/PC into NetPro
Using the following operator input sequence steps, you can integrate a PC/PG into NetPro:
1. Click on the "NetPro" button (see figure above).
2. From the catalog under "Stations", insert the PG/PC via Drag&Drop into the network
configuration (see figure below).

Table of Contents

Related product manuals