EasyManua.ls Logo

Siemens SINUMERIK 804D sl

Siemens SINUMERIK 804D sl
319 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connect PG/PC with the PLC
6.2 Setting up the communication
CNC Part 1 (NCK, PLC, drive)
40 Commissioning Manual, 11/2006, 6FC5397-2AP10-2BA0
6.2 Setting up the communication
Introduction
To load the configuration into the PLC, the communications connection (Ethernet) from
PG/PC to the PLC required for the loading must be secured.
Operator input sequence steps for establishing a communications connection to the PLC
The communications connection to the PLC may be set from PG/PC via SIMATIC Manager
with the following operator input sequence steps:
1. Select menu command: "Set Extras > PG/PC interface..."
2. On the Access Mode tab look for the interface used, in the selection field
"Parameterization of used interface", for instance: "TCP/IP -> Realtek RTL8139/810x
F…"
3. Confirm the parameterization with "OK".
Note
Parameterization of the PG/PC interface can be performed or changed from the SIMATIC
Manager at any time.

Table of Contents

Related product manuals