Table 11-8 Type 2N
Head type AH0, AV0, SI‐
TRANS TF
AG0, UG0 AU0, UU0
T
max
head 85 °C 100 °C 120 °C
Temperature class T6 T4 T3 T4
Max. permitted pow‐
er consumption of
electronic (W)
0 ... 3
1)
With or without
electronic
0
Without elec‐
tronic
1 ... 3
1)
With electronic
0
Without elec‐
tronic
1 ... 3
1)
With electronic
Medium temper‐
ature (°C)
T
a_max
in °C T
a_max
in °C T
a_max
in °C T
a_max
in °C T
a_max
in °C
100 °C 60 100 70 120 65
80 °C 67 100 77 120 72
1)
For the determination of ambient temperatures, maximum enclosure temperature of 85 °C was taken as a basis when
electronic are incorporated.
Technical data
11.1 Rated conditions
SITRANS TS100/TS200/TS300/TS500/TSinsert/TSthermowell
136 Operating Instructions, 08/2020, A5E47810090-AA