5
Initial Operation
Before you switch on the system for the first time, check the wiring to
make sure that the connections are correct and firmly seated.
1.
Then switch on the voltage.
2.
Test the function of the solenoid valves (348) in the service menu
(parameter 4.3.1).
3.
Test the functions of the temperature sensor and the pulse inputs in
the service menu, too.
4.
Check whether the correct pulse transmitter parameter has been set
(parameter 3.3.1.4).
The default parameter is a pulse transmitter with a THS switch output.
Test the printer connection by printing a zero receipt.
☺ Once all these tests have been run successfully, you can start parameter
setting of the MultiFlow.
The MultiFlow has an access check for sensitive parameter areas.
The following passwords are set by the manufacturer:
The input of parameters and a description of the menu structure are
detailed from chapter 9 "Configuration of the MultiFlow" / page 119
onwards.
5.1 Version Numbers
Version numbers, which are printed on the parameter lists and W & M
receipts, are used to identify the current software version.
These numbers can be called up in menu 4.1.1.