Appendix B. RF Test Cases of the TC-3000C
237
1. Hopping mode parameter specifies which hopping sequence will be used for the test.
Allowed values of the parameter are:
1 - single frequency (hopping is off)
5 - reduced hopping sequence
79 - hopping is on
2. BT channels are the RX frequency channels of the DUT, which are selected to test. The
frequency for each channel is calculated as (2402+ch) MHz, where ch is the frequency
channel. The frequency channel is the value from 0 to 78. Any quantity of the frequency
channels can be selected in the TC-3000C. The list of selected channels must be
separated by “-“. For instance, the record “0-20-40-60” means that the test case must be
executed for four frequency channels: 0, 20, 40 and 60, that is for the frequencies 2402
MHz, 2422 MHz, 2442 MHz and 2462 MHz. This parameter is meaningful only if the
Hopping mode parameter is equal to 1 (hoping is off).
3. RX power is expected power at the input of the DUT’s receiver, measured in dBm.
4. Number of samples is the minimum number of returned payload bytes from the DUT.
If the flag “Use Default” is selected then all of displayed values of parameters are ignored and
the listed above values will be assigned automatically:
Hopping mode: 1 (Hopping is off)
BT channels: 0-39-78
RX Power: -70 dBm
Number of samples: 200,000 bytes
Additional test conditions
Test mode is Loop back, hopping is off, whitening is disabled, the packet type is DH1, the
payload’s bit pattern is PRBS9.
Test Procedure
1. The tester calculates and sets the TX power to satisfy requirement of expected power at
the input of the DUT’s receiver. The TX power is calculated as P
TX
= P
RX
DUT
+ PL, where
P
TX
is the TX power of the tester, P
RX
DUT
is the expected power at the input of the DUT’s
receiver and PL is the path losses. To set the path losses value use Menu
Configuration DUT More1/5 PathLoss.
2. If the DUT is not connected then the tester creates connection via access procedures
(paging and inquiry if necessary).
3. The tester will activate test mode (if the test mode is not activated yet) and will set all
necessary parameters of the test mode.
4. The tester checks whether the DUT transmits at maximum power. If not and the DUT
supports power control, then the tester will consecutively send LMP_incr_power_req
requests until the LMP_max_power response would be received from the DUT. The time
delay between two consequential LMP_incr_power_req requests depends on the
Pow.SetTime parameter (to modify the value use: Menu Configuration DUT
More3/5 Pow.SetTime, default value is equal to 1 second).).
5. The DUT is set to receive at the given channel frequency. The tester continuously sends
DH1 packets to the DUT at the given channel frequency.
6. The tester enters dirty transmitter mode [1] and starts the bit error rate measurement.
Tester stops the measurement if the number of returned and processed payload bytes
exceeds required number (see the Number of samples parameter). Tester records actual
number of processed samples and number of bitts with error.
7. Tester stops dirty transmitter mode.