EasyManua.ls Logo

TSI Quest EVM-7 - Figure 3-7: PID Correction Factor; Figure 3-8: PID Correction Factor Displayed on

TSI Quest EVM-7
178 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting up Parameters via the Keypad
PID Sensor Setup
EVM Series User Manual
26
Setting PID correction factor and/or ppb zero cal
1. From the start menu, press / Arrows to select Setup and press Enter
.
2. Select PID by pressing / Arrows and press Enter
.
3. In the PID screen, select either ppb zero cal or the PID factor by pressing /Arrows.
4. Press Enter
to move to either the disabled/enabled field or the value field. Press /
Arrows to change the value. Press Enter
to save your changes.
5. Press On/Off/Esc
repeatedly to return to the start screen.
PPB Zero Cal
Press up/down arrows to select either
enabled/disabled. Press Enter to save.
PID Factor
Press up/down arrows on keypad to change value.
Press Enter to save.
Default soft key
Press to restore PID factor to default (“1”).
Figure 3-7: PID correction factor/ppb setup
NOTE: When changing PID factor to a value excluding “1”, the PID correction factor will
appear as a subscript on the measurement screens. Two samples are displayed
below:
PID and correction factor
The applied correction factor “3.5” is
displayed in the Gas measurement screen.
PID and correction factor
Displayed in the Composite
measurement screen.
Figure 3-8: PID correction factor displayed on measurement screens

Table of Contents

Related product manuals