Installation Pipe System TITANUS MICRO·SENS
®
6 – 2 Data: 01/09 MS_A_06-en-e
Adhesives and cleaning products contain solvents and are flammable. It
is essential to observe the supplier’s safety information before process-
ing.
3. Keep the pipe lengths and direction changes to a minimum. Elbows
and bends have an extremely high flow resistance. Use them only
where this is unavoidable. Should this be necessary, the pipe length
must then be reduced in relation to the fitted bends
1
.
Arcs should be used instead of elbows. If there are too many direction
changes, an air flow fault can occur in TITANUS
®
and detection time can
be affected.
4. The pipes must be installed in such a way that they do not sag or mo-
ve. They are fixed with pipe clips without rubber core. The space be-
tween the pipe clips should be no more than 80cm. Reduce the space
between clips to no more than 30cm if there are high temperature
variations.
Do not use pipe clips with rubber cores as these do not expand length-
wise and the pipes would sag or crack.
5. Close open pipe ends with end caps.
After pipe installation is complete, check for the following:
- air tightness (e.g. due to damage)
- any faulty connections
- correct projection of the air sampling points
1
An arc equals a straight piece of pipe of 0.3m
an elbow equals a straight piece of pipe of 1.5m