EasyManuals Logo

Xinje XD Series User Manual

Xinje XD Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #285 background imageLoading...
Page #285 background image
284
Receive data [RCV]
1) Summary
Write the specified remote station no’s data to local device.
Send data [RCV]
16 bits
instruction
RCV
32 bits
instruction
-
Execution
condition
Normally ON/OFF, rising
edge triggering
Suitable
model
XD, XL
Hardware
V3.2.3 and higher version
Software
V3.2.2 and higher version
2)Operands
Operands
Function
Type
S1
Local data starting address
16 bits, BIN
S2
Receivebyte number or soft component address
16 bits, BIN
n
Communication port no.
16 bits, BIN
3)Suitable soft component
Operan
ds
Word soft elements
Bit soft elements
System
Consta
nt
Module
System
D
F
D
T
D
C
D
D
X
D
Y
D
M
D
S
K/H
I
D
Q
D
X
Y
M
S
T
C
Dn.
m
S1
S2
n
K
*Notes: D includes D, HD; TD includes TD, HTD; CD includes CD, HCD, HSCD, HSD; DM
includes DM, DHM; DS includes DS, DHS. M includes M, HM, SM; S includes S, HS; T
includes T, HT; C includes C, HC.
RCV D20 D200 K2
S1·
S2·
n
M1
Data receiving instructions, M1's rising edge receives data once.
Communication port. Scope: K0 ~ K5. K0: Port0 (RS232), K1: Port1(RS232), K2:
Port2(RS485), K3: Port3(left extension port), K4: Port4(above extension port 1), K5:
Port5(above extension port 2).
After receiving the data, the "received" flag SM163 (communication port 2) is set on.
Function and action
tudonghoatoancau.com

Table of Contents

Other manuals for Xinje XD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje XD Series and is the answer not in the manual?

Xinje XD Series Specifications

General IconGeneral
Input Voltage24V DC
Storage Temperature-20°C to 70°C
Protection ClassIP20
TypePLC
SeriesXD
Programming LanguageLadder Logic, Instruction List
Communication InterfaceRS232, RS485
Power Supply24V DC
Digital InputsAvailable (number varies by model)
Digital OutputsAvailable (number varies by model)
Analog InputsAvailable (number varies by model)
Analog OutputsAvailable (number varies by model)
Output TypeRelay, Transistor
Number of InputsVaries by model (see Digital Inputs and Analog Inputs)
Number of OutputsVaries by model (see Digital Outputs and Analog Outputs)
Operating Temperature0°C to 50°C
Humidity5% to 95% (non-condensing)