305
S3+17
PID max output
0~32767
Internal use
parameters of the
system for
monitoring purposes
only
S3+18
PID min output
0~32767
Internal use
parameters of the
system for
monitoring purposes
only
S3+19
Last time sampling time
0~sampling time (unit: ms)
16-bit no sign,
Internal use
parameters of the
system for
monitoring purposes
only
S3+20
Actual sampling time
space
The value is around the
sampling time
32-bit no sign,
Internal use
parameters of the
system for
monitoring purposes
only
S3+22
Last time user set target
temperature
The value before changing the
target temperature
Internal use
parameters of the
system for
monitoring purposes
only
S3+23
-
-
Parameter is
reserved
The following is the joint address (divided into step setting, critical oscillation setting and
manual control)
Step part (read only parameters, only for monitoring)
S3+24
Actual sampling space
0~4294967296 (unit: ms)
Internal usage
parameters of the
system
S3+26
Operating segment of
auto-tuning PID
0: Preparation stage
1~2: auto tune parameter
collection
3: calculate PID parameters
Internal usage
parameters of the
system
S3+28
Duration of auto-tuning
PID operating
parameters
0~4294967296 (unit: ms)
Internal usage
parameters of the
system
S3+30
Real-time accumulation
of two inflection points
Clear and recalculate the time
when reaching the inflection
point0~4294967296(unit: ms)
Internal usage
parameters of the
system
S3+32
Sampling variation of
inflection point
Sampling difference between two
inflection points
-2147483648~2147483647
Internal usage
parameters of the
system
S3+34
Sampling interval time
of inflection point EK
0~4294967296 (unit: ms)
Internal usage
parameters of the
system
S3+36
Time from auto-tuning
PID to inflection point
0~4294967296 (unit: ms)
Internal usage
parameters of the
tudonghoatoancau.com

Table of Contents

Other manuals for Xinje XD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje XD Series and is the answer not in the manual?

Xinje XD Series Specifications

General IconGeneral
Input Voltage24V DC
Storage Temperature-20°C to 70°C
Protection ClassIP20
TypePLC
SeriesXD
Programming LanguageLadder Logic, Instruction List
Communication InterfaceRS232, RS485
Power Supply24V DC
Digital InputsAvailable (number varies by model)
Digital OutputsAvailable (number varies by model)
Analog InputsAvailable (number varies by model)
Analog OutputsAvailable (number varies by model)
Output TypeRelay, Transistor
Number of InputsVaries by model (see Digital Inputs and Analog Inputs)
Number of OutputsVaries by model (see Digital Outputs and Analog Outputs)
Operating Temperature0°C to 50°C
Humidity5% to 95% (non-condensing)