6 Functional Description of the Ethernet Modules
6-38
Two single-color LEDs are provided on the RJ45 connector, indicating the current
communication state. Although these LEDs are not labeled, they can be clearly identi-
fied through their color. The upper, yellow LED indicates the link state, the lower,
green LED indicates that communication is active.
10BaseT Link LED
OFF No active link. Communication is not possible.
Yellow static Active link. Communication is possible.
10BaseT Active LED
Off No communication.
Green flashing Communicating.
6.7.2 Hardware structure
The 10BaseT module EI 813F comprises the following hardware components:
LAN controller/coprocessor, adapted to Intel RISC-CPU
32-bit data bus, 32-bit address bus, DMA, interrupt
Serial interface/Manchester encoder for generating a serial bit stream
EEPROM for configuration data
HEX coding switch for configuring IP address / redundancy link
Electrical isolation for TP interface
ESD protector on RJ45 socket
Isolator for electrical isolation of the bus signals
Buffer battery holder with polarity reversal protection and monitoring circuit
RJ45 connector