3 Mounting the AC 800F
3-8
3.1.4 Wall mounting on top hat rails
If the device is mounted outside a cabinet or switch box, the
special contact ledge RW 855F must be used.
When mounting the devices to the top hat rails, make sure that
they are positioned properly and that the rail clamping spring
snaps in.
When attaching the AC 800F to a
wall-mounted rail, several other
devices can be placed on the
same rail.
Select the appropriate pegs
- depending on the wall material -
and fasten the rail with two
6 × 60 mm screws, as described
in Section 3.1.3.
Fig. 3-9 Wall mounting on top hat rail
Risk of overheating !
Minimum spacing above and below: 150 mm (3.375 HU).
Max. temperature at the AC 800F bottom side (air intake):
60 °
°°
°C
Keep air vents open !
Do not impair air flow through AC 800F.
If the device is mounted outside a cabinet, the special contact
ledge RW 855F must be used.