3.12.4 Settings
Table 41: Non group settings
Parameter
Values (Range) Unit Step Default Description
Input mode 1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
1=Not in use Analogue input mode
Input maximum 0...2000 Ω 1 2000 Maximum analogue input value for mA or
resistance scaling
Input minimum 0...2000 Ω 1 0 Minimum analogue input value for mA or
resistance scaling
Value unit 1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
1=Dimensionless Selected unit for output value format
Value maximum -10000.0...10000.0 1 10000.0 Maximum output value for scaling and
supervision
Value minimum -10000.0...10000.0 1 -10000.0 Minimum output value for scaling and
supervision
Val high high limit -10000.0...10000.0 1 10000.0 Output value high alarm limit for
supervision
Value high limit -10000.0...10000.0 1 10000.0 Output value high warning limit for
supervision
Value low limit -10000.0...10000.0 1 -10000.0 Output value low warning limit for
supervision
Value low low limit -10000.0...10000.0 1 -10000.0 Output value low alarm limit for
supervision
Value deadband 100...100000 1 1000 Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Table 42: Non group settings
Parameter
Values (Range) Unit Step Default Description
Input mode 1=Not in use
5=0..20mA
1=Not in use Analogue input mode
Input maximum 0...20 mA 1 20 Maximum analogue input value for mA or
resistance scaling
Input minimum 0...20 mA 1 0 Minimum analogue input value for mA or
resistance scaling
Value unit 1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
1=Dimensionless Selected unit for output value format
Table continues on next page
1MRS758755 A Section 3
Basic functions
REC615 and RER615 99