13.4.7.1 COM0022 and COM0023 jumper locations and connections
The optional communication module COM0022 supports EIA-232/EIA-485 serial
communication (X6 connector). Only COM1 (X6 connector) is used for serial
communication.
Connector X5 on COM0022 is dedicated to IRIG-B.
Table 718: Configuration options of the communication port for COM0022
COM1 connector X6
EIA-232
EIA-485 2-wire
EIA-485 4-wire
The optional communication module COM0023 supports EIA-232/EIA-485 serial
communication (X6 connector), EIA-485 serial communication (X5 connector) and
optical ST serial communication (X12 connector).
Two independent communication ports are supported by COM0023. The two 2-wire
ports use COM1 and COM2. Alternatively, if only one 4-wire port is configured, it
uses COM2. The fibre-optic ST connection uses the COM1 port.
Table 719: Configuration options of the communication ports for COM0023
COM1 connector X6
COM2 connector X5 or X12
EIA-232 Optical ST (X12)
EIA-485 2-wire EIA-485 2-wire (X5)
EIA-485 4-wire EIA-485 4-wire (X5)