4.6.1.8 Monitored data
Table 482: DPSRDIR Monitored data
Name
Type Values (Range) Unit Description
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic
angle
DPSRDIR
Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.7 Multipurpose protection MAPGAPC
4.7.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multipurpose protection MAPGAPC MAP MAP
4.7.2 Function block
GUID-A842A2C8-0188-4E01-8490-D00F7D1D8719 V2 EN
Figure 232: Function block
4.7.3 Functionality
The multipurpose protection function MAPGAPC is used as a general protection with
many possible application areas as it has flexible measuring and setting facilities. The
function can be used as an under- or overprotection with a settable absolute hysteresis
limit. The function operates with the definite time (DT) characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
the definite timer or the function itself, if desired.
4.7.4 Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
1MRS758755 A Section 4
Protection functions