Name Type Values (Range) Unit Description
Variation Dur Ph B FLOAT32 0.000...3600.000 s Variation duration Phase
B
Var Dur Ph B time Timestamp Variation Ph B start time
stamp
Variation Dur Ph C FLOAT32 0.000...3600.000 s Variation duration Phase
C
Var Dur Ph C time Timestamp Variation Ph C start time
stamp
Var current Ph A FLOAT32 0.00...60.00 xIn Current magnitude
Phase A preceding
variation
Var current Ph B
FLOAT32 0.00...60.00 xIn Current magnitude
Phase B preceding
variation
Var current Ph C
FLOAT32 0.00...60.00 xIn Current magnitude
Phase C preceding
variation
10.3.10 Technical data
Table 699: PHQVVR Technical data
Characteristic
Value
Operation accuracy ±1.5% of the set value or ±0.2% of reference
voltage
Reset ratio Typically 0.96 (Swell), 1.04 (Dip, Interruption)
10.4 Voltage unbalance VSQVUB
10.4.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage unbalance VSQVUB PQUUB PQVUB
10.4.2 Function block
GUID-568233FA-CCCC-4D0F-998A-52F9F12AC0F9 V2 EN
Figure 371: Function block
Section 10 1MRS758755 A
Power quality measurement functions
698 REC615 and RER615
Technical Manual