Parameter Values (Range) Unit Step Default Description
Vendor 0 External equipment vendor
Serial number 0 External equipment serial number
Model 0 External equipment model
Table 635: DCXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation mode on/off
Select timeout 10000...300000 ms 10000 30000 Select timeout in ms
Pulse length 10...60000 ms 1 100 Open and close pulse length
Control model 0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
4=sbo-with-
enhanced-security
Select control model
Operation timeout 10...60000 ms 1 30000 Timeout for negative termination
Identification DCXSWI1 switch
position
Control Object identification
Table 636: DCXSWI Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Operation counter 0...10000 1 0 Breaker operation cycles
Adaptive pulse 0=False
1=True
1=True Stop in right position
Event delay 0...60000 ms 1 10000 Event delay of the intermediate position
Vendor 0 External equipment vendor
Serial number 0 External equipment serial number
Model 0 External equipment model
9.1.8 Monitored data
Table 637: CBXCBR Monitored data
Name
Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position
indication
Table 638: DCXSWI Monitored data
Name
Type Values (Range) Unit Description
POSITION Dbpos 0=intermediate
1=open
2=closed
3=faulty
Apparatus position
indication
Section 9 1MRS758755 A
Control functions
612 REC615 and RER615
Technical Manual