3.16.16.4 Signals
Table 188: UDFCNT Input signals
Name
Type Default Description
UP_CNT BOOLEAN 0=False Input for up counting
DOWN_CNT BOOLEAN 0=False Input for down counting
RESET BOOLEAN 0=False Reset input for counter
LOAD BOOLEAN 0=False Load input for counter
Table 189: UDFCNT Output signals
Name Type Description
UPCNT_STS BOOLEAN Status of the up counting
DNCNT_STS BOOLEAN Status of the down counting
3.16.16.5 Settings
Table 190: UDFCNT Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Counter load value 0...2147483647 1 10000 Preset counter value
Reset counter 0=Cancel
1=Reset
0=Cancel Resets counter value
Load counter 0=Cancel
1=Load
0=Cancel Loads the counter to preset value
3.16.16.6 Monitored data
Table 191: UDFCNT Monitored data
Name
Type Values (Range) Unit Description
CNT_VAL INT64 0...2147483647 Output counter value
3.17 Factory settings restoration
In case of configuration data loss or any other file system error that prevents the
protection relay from working properly, the whole file system can be restored to the
original factory state. All default settings and configuration files stored in the factory
are restored. For further information on restoring factory settings, see the operation
manual.
Section 3 1MRS758755 A
Basic functions
178 REC615 and RER615
Technical Manual