Name Type Values (Range) Unit Description
AI_RANGE5 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
9-10-11c, range
AI_DB6 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
13-14-12c, reported
value
AI_RANGE6
Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
13-14-12c, range
AI_DB7 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
15-16-12c, reported
value
AI_RANGE7
Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
15-16-12c, range
AI_DB8 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
17-18-12c, reported
value
AI_RANGE8
Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
17-18-12c, range
3.13 SMV function blocks
SMV function blocks are used in the process bus applications with the sending of the
sampled values of analog currents and voltages and with the receiving of the sampled
values of voltages.
3.13.1 IEC 61850-9-2 LE sampled values sending SMVSENDER
3.13.1.1 Functionality
The SMVSENDER function block is used for activating the SMV sending
functionality. It adds/removes the sampled value control block and the related data set
into/from the sending device's configuration. It has no input or output signals.
SMVSENDER can be disabled with the Operation setting value “off”. If the
SMVSENDER is disabled from the LHMI, it can only be enabled from the LHMI.
When disabled, the sending of the samples values is disabled.
1MRS758755 A Section 3
Basic functions
REC615 and RER615 101