EasyManua.ls Logo

ABB RELION Series - Monitored Data

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
Life alarm level 0...99999 1 500 Alarm level for CB remaining life
Pressure alarm time 0...60000 ms 1 10 Time delay for gas pressure alarm in ms
Pres lockout time 0...60000 ms 10 10 Time delay for gas pressure lockout in ms
Ini inactive days 0...9999 1 0 Initial value of the inactive days counter
Inactive Alm hours 0...23 h 1 0 Alarm time of the inactive days counter in
hours
7.1.8 Monitored data
Table 560: SSCBR Monitored data
Name Type Values (Range) Unit Description
T_TRV_OP FLOAT32 0...60000 ms Travel time of the CB
during opening operation
T_TRV_CL FLOAT32 0...60000 ms Travel time of the CB
during closing operation
T_SPR_CHR FLOAT32 0.00...99.99 s The charging time of the
CB spring
NO_OPR INT32 0...99999 Number of CB operation
cycle
INA_DAYS INT32 0...9999 The number of days CB
has been inactive
CB_LIFE_A INT32 -99999...99999 CB Remaining life phase
A
CB_LIFE_B INT32 -99999...99999 CB Remaining life phase
B
CB_LIFE_C INT32 -99999...99999 CB Remaining life phase
C
IPOW_A FLOAT32 0.000...30000.00
0
Accumulated currents
power (Iyt), phase A
IPOW_B FLOAT32 0.000...30000.00
0
Accumulated currents
power (Iyt), phase B
IPOW_C FLOAT32 0.000...30000.00
0
Accumulated currents
power (Iyt), phase C
SSCBR Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 A Section 7
Condition monitoring functions
REC615 and RER615 551
Technical Manual

Table of Contents

Other manuals for ABB RELION Series

Related product manuals