EasyManua.ls Logo

ABB RELION Series - Monitored Data

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
Value maximum -10000.0...10000.0 1 10000.0 Maximum output value for scaling and
supervision
Value minimum -10000.0...10000.0 1 -10000.0 Minimum output value for scaling and
supervision
Val high high limit -10000.0...10000.0 1 10000.0 Output value high alarm limit for
supervision
Value high limit -10000.0...10000.0 1 10000.0 Output value high warning limit for
supervision
Value low limit -10000.0...10000.0 1 -10000.0 Output value low warning limit for
supervision
Value low low limit -10000.0...10000.0 1 -10000.0 Output value low alarm limit for
supervision
Value deadband 100...100000 1 1000 Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
3.12.5 Monitored data
Table 43: Monitored data
Name Type Values (Range) Unit Description
AI_DB1 FLOAT32 -10000.0...10000
.0
mA input, Connectors
1-2, reported value
AI_RANGE1 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors
1-2, range
AI_DB2 FLOAT32 -10000.0...10000
.0
mA input, Connectors
3-4, reported value
AI_RANGE2 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Connectors
3-4, range
AI_DB3 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
5-6-11c, reported value
AI_RANGE3 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
5-6-11c, range
AI_DB4 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
7-8-11c, reported value
AI_RANGE4 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
7-8-11c, range
AI_DB5 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
9-10-11c, reported value
Table continues on next page
Section 3 1MRS758755 A
Basic functions
100 REC615 and RER615
Technical Manual

Table of Contents

Other manuals for ABB RELION Series

Related product manuals