IRIG-B time synchronization requires a COM card with an IRIG-B
input.
3.4.1.3 Signals
3.4.1.4 Settings
Table 11: Non group settings
Parameter Values (Range) Unit Step Default Description
Time format 1=24H:MM:SS:MS
2=12H:MM:SS:MS
1=24H:MM:SS:M
S
Time format
Date format 1=DD.MM.YYYY
2=DD/MM/YYYY
3=DD-MM-YYYY
4=MM.DD.YYYY
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
1=DD.MM.YYYY Date format
Table 12: Non group settings
Parameter
Values (Range) Unit Step Default Description
Synch source 0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
17=IEC60870-5-10
3
1=SNTP Time synchronization source
PTP domain ID 0...255 1 0 The domain is identified by an integer, the
domainNumber, in the range of 0 to 255.
PTP priority 1 0...255 1 128 PTP priority 1, in the range of 0 to 255.
PTP priority 2 0...255 1 128 PTP priority 2, in the range of 0 to 255.
PTP announce mode 1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588 PTP announce frame mode
Table 13: Non group settings
Parameter
Values (Range) Unit Step Default Description
Date 0 Date
Time 0 Time
Local time offset -840...840 min 1 0 Local time offset in minutes