Table 177: SPCGAPC Output signals
Name Type Description
O1 BOOLEAN Output 1 status
O2 BOOLEAN Output 2 status
O3 BOOLEAN Output 3 status
O4 BOOLEAN Output 4 status
O5 BOOLEAN Output 5 status
O6 BOOLEAN Output 6 status
O7 BOOLEAN Output 7 status
O8 BOOLEAN Output 8 status
O9 BOOLEAN Output 9 status
O10 BOOLEAN Output 10 status
O11 BOOLEAN Output 11 status
O12 BOOLEAN Output 12 status
O13 BOOLEAN Output 13 status
O14 BOOLEAN Output 14 status
O15 BOOLEAN Output 15 status
O16 BOOLEAN Output 16 status
3.16.12.4 Settings
Table 178: SPCGAPC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Loc Rem restriction 0=False
1=True
1=True Local remote switch restriction
Operation mode 0=Pulsed
1=Toggle/
Persistent
-1=Off
-1=Off Operation mode for generic control point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation mode
Description SPCGAPC1
Output 1
Generic control point description
Operation mode 0=Pulsed
1=Toggle/
Persistent
-1=Off
-1=Off Operation mode for generic control point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation mode
Description SPCGAPC1
Output 2
Generic control point description
Operation mode 0=Pulsed
1=Toggle/
Persistent
-1=Off
-1=Off Operation mode for generic control point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation mode
Table continues on next page
Section 3 1MRS758755 A
Basic functions
164 REC615 and RER615
Technical Manual