Table 140: DTMGAPC Output signals
Name Type Description
Q BOOLEAN Output status
3.16.4.7 Settings
Table 141: DTMGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Monday Act enable 0=False
1=True
false Activation / deactivation need on Monday
Monday Act hour 0...23 h 8 Activation hour time for Monday
Monday Act Mn 0...59 min 0 Activation minute time for Monday
Monday off delay 1...1440 min 1 60 Activation duration for Monday
Tuesday Act enable 0=False
1=True
false Activation / deactivation need on Tuesday
Tuesday Act hour 0...23 h 8 Activation hour time for Tuesday
Tuesday Act Mn 0...59 min 0 Activation minute time for Tuesday
Tuesday off delay 1...1440 min 1 60 Activation duration for Tuesday
Wednesday Act enable 0=False
1=True
false Activation / deactivation need on
Wednesday
Wednesday Act hour 0...23 h 8 Activation hour time for Wednesday
Wednesday Act Mn 0...59 min 0 Activation minute time for Wednesday
Wednesday off delay 1...1440 min 1 60 Activation duration for Wednesday
Thursday Act enable 0=False
1=True
false Activation / deactivation need on
Thursday
Thursday Act hour 0...23 h 8 Activation hour time for Thursday
Thursday Act Mn 0...59 min 0 Activation minute time for Thursday
Thursday off delay 1...1440 min 1 60 Activation duration for Thursday
Friday Act enable 0=False
1=True
false Activation / deactivation need on Friday
Friday Act hour 0...23 h 8 Activation hour time for Friday
Friday Act Mn 0...59 min 0 Activation minute time for Friday
Friday off delay 1...1440 min 1 60 Activation duration for Friday
Saturday Act enable 0=False
1=True
false Activation / deactivation need on Saturday
Saturday Act hour 0...23 h 8 Activation hour time for Saturday
Saturday Act Mn 0...59 min 0 Activation minute time for Saturday
Saturday off delay 1...1440 min 1 60 Activation duration for Saturday
Sunday Act enable 0=False
1=True
false Activation / deactivation need on Sunday
Table continues on next page