3.16.5.4 Settings
Table 145: TOFGAPC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Off delay time 1 0...3600000 ms 10 0 Off delay time
Off delay time 2 0...3600000 ms 10 0 Off delay time
Off delay time 3 0...3600000 ms 10 0 Off delay time
Off delay time 4 0...3600000 ms 10 0 Off delay time
Off delay time 5 0...3600000 ms 10 0 Off delay time
Off delay time 6 0...3600000 ms 10 0 Off delay time
Off delay time 7 0...3600000 ms 10 0 Off delay time
Off delay time 8 0...3600000 ms 10 0 Off delay time
3.16.5.5 Technical data
Table 146: TOFGAPC Technical data
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
3.16.6 Time delay on (8 pcs) TONGAPC
3.16.6.1 Function block
GUID-B694FC27-E6AB-40FF-B1C7-A7EB608D6866 V1 EN
Figure 91: Function block
3.16.6.2 Functionality
The time delay on (8 pcs) function TONGAPC can be used, for example, for time-
delaying the output related to the input signal. TONGAPC contains eight independent
timers. The timer has a settable time delay. Once the input is activated, the output is
set after the time set by the On delay time setting has elapsed.
Section 3 1MRS758755 A
Basic functions
144 REC615 and RER615
Technical Manual