Analog output range is from -2000000.0 to 2000000.0.
If the value of the AIn_VALUE input exceeds the analog input range,
AOn_VALUE is set to 0.0.
If the result of AIn_VALUE multiplied by the Scale ratio n setting
exceeds the analog output range, AOn_VALUE shows the minimum or
maximum value, according to analog value range.
3.16.10.3 Signals
Table 160: SCA4GAPC Input signals
Name Type Default Description
AI1_VALUE FLOAT32 0.0 Analog input value of channel 1
AI2_VALUE FLOAT32 0.0 Analog input value of channel 2
AI3_VALUE FLOAT32 0.0 Analog input value of channel 3
AI4_VALUE FLOAT32 0.0 Analog input value of channel 4
Table 161: SCA4GAPC Output signals
Name
Type Description
AO1_VALUE FLOAT32 Analog value 1 after scaling
AO2_VALUE FLOAT32 Analog value 2 after scaling
AO3_VALUE FLOAT32 Analog value 3 after scaling
AO4_VALUE FLOAT32 Analog value 4 after scaling
3.16.10.4 Settings
Table 162: SCA4GAPC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Scale ratio 1 0.001...1000.000 0.001 1.000 Scale ratio for analog value 1
Scale ratio 2 0.001...1000.000 0.001 1.000 Scale ratio for analog value 2
Scale ratio 3 0.001...1000.000 0.001 1.000 Scale ratio for analog value 3
Scale ratio 4 0.001...1000.000 0.001 1.000 Scale ratio for analog value 4