L/R Control L/R Control status Control access
Control FB input
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev L/R state
CTRL.LLN0.LocKeyHMI
Local user IEC 61850
client
2)
IEC 61850
client
3)
CTRL_REM
4)
TRUE TRUE 3 x
CTRL_REM FALSE TRUE 7 x x
CTRL_ALL FALSE TRUE 6 x x x
CTRL_ALL
4)
TRUE TRUE 5 x x
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC61850 command originator category is remote.
3) Client IEC61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.16.11.8 Signals
Table 172: CONTROL input signals
Name Type Default Description
CTRL_OFF BOOLEAN 0 Control input OFF
CTRL_LOC BOOLEAN 0 Control input Local
CTRL_STA BOOLEAN 0 Control input Station
CTRL_REM BOOLEAN 0 Control input Remote
CTRL_ALL BOOLEAN 0 Control input All
Table 173: CONTROL output signals
Name
Type Description
OFF BOOLEAN Control output OFF
LOCAL BOOLEAN Control output Local
STATION BOOLEAN Control output Station
REMOTE BOOLEAN Control output Remote
ALL BOOLEAN Control output All
BEH_BLK BOOLEAN Logical device CTRL block
status
BEH_TST BOOLEAN Logical device CTRL test status
1MRS758755 A Section 3
Basic functions
REC615 and RER615 159
Technical Manual