Parameter Values (Range) Unit Step Default Description
Operation mode 0=Pulsed
1=Persistent
-1=Off
-1=Off Operation mode for generic control point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation mode
Description SPCRGAPC1
Output 16
Generic control point description
3.16.14 Local generic control points SPCLGAPC
3.16.14.1 Function block
GUID-2182EB7C-0709-4807-B6B2-508B2A5949C0 V1 EN
Figure 105: Function block
3.16.14.2 Functionality
The local generic control points function SPCLGAPC is dedicated only for local
controlling, that is, SPCLGAPC cannot be controlled remotely. The local control is
done through the buttons in the front panel.
3.16.14.3 Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
SPCLGAPC has the Operation mode, Pulse length and Description settings available
to control all 16 outputs. By default, the Operation mode setting is set to "Off". This
disables the controllable signal output. SPCLGAPC also has a general setting Loc
Rem restriction, which enables or disables the local or remote state functionality.
When the Operation mode is set to "Toggle", the corresponding output toggles
between "True" and "False" for every input pulse received. The state of the output is
stored in a nonvolatile memory and restored if the protection relay is restarted.
1MRS758755 A Section 3
Basic functions
REC615 and RER615 171
Technical Manual