Parameter Values (Range) Unit Step Default Description
Operation mode 0=Pulsed
1=Persistent
-1=Off
-1=Off Operation mode for generic control point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation mode
Description SPCLGAPC1
Output 16
Generic control point description
3.16.15 Programmable buttons (4 buttons) FKEY4GGIO
3.16.15.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Programmable buttons (4 buttons) FKEY4GGIO FKEY4GGIO FKEY4GGIO
3.16.15.2 Function block
FKEY4GGIO
K2
K1
K3
K4
L2
L1
L3
L4
GUID-6DBCE16B-0F2A-4C0C-BBAC-0293D9E1EB8B V1 EN
Figure 106: Function block
3.16.15.3 Functionality
The Programmable buttons function FKEY4GGIO is a simple interface between the
panel and the application. The user input from the buttons available on the front panel
is transferred to the assigned functionality and the corresponding LED is turned ON
or OFF for indication. The behavior of each function key in the specific application is
configured by connection with other application functions. This gives maximum
flexibility.
3.16.15.4 Operation principle
Inputs L1...L4 represent the LEDs on the relay's LHMI. When an input is set to
TRUE, the corresponding LED is lit. When a function key on the LHMI is pressed, the
corresponding output K1...K4 is set to TRUE.
Each function key has settable text descriptions for the on and off states. The visibility
of function key text descriptions on the LHMI can be selected with setting parameter
Function key text visibility.
1MRS758755 A Section 3
Basic functions
REC615 and RER615 175
Technical Manual