Parameter Values (Range) Unit Step Default Description
Protection crd limit 1...5 1 1 Protection coordination shot limit
Protection crd mode 1=No condition
2=AR inoperative
3=CB close manual
4=AR inop, CB man
5=Always
4=AR inop, CB
man
Protection coordination mode
Control line 0...63 1 63 Control line, defines INIT inputs which are
protection signals
Enable shot jump 0=False
1=True
1=True Enable shot jumping
CB closed Pos status 0=False
1=True
0=False Circuit breaker closed position status
Blk signals CBB1 0...63 1 0 Blocking lines for CBB1
Blk signals CBB2 0...63 1 0 Blocking lines for CBB2
Blk signals CBB3 0...63 1 0 Blocking lines for CBB3
Blk signals CBB4 0...63 1 0 Blocking lines for CBB4
Blk signals CBB5 0...63 1 0 Blocking lines for CBB5
Blk signals CBB6 0...63 1 0 Blocking lines for CBB6
Blk signals CBB7 0...63 1 0 Blocking lines for CBB7
Str 2 delay shot 1 0...300000 ms 10 0 Delay time for start2, 1st reclose
Str 2 delay shot 2 0...300000 ms 10 0 Delay time for start2 2nd reclose
Str 2 delay shot 3 0...300000 ms 10 0 Delay time for start2 3rd reclose
Str 2 delay shot 4 0...300000 ms 10 0 Delay time for start2, 4th reclose
Str 3 delay shot 1 0...300000 ms 10 0 Delay time for start3, 1st reclose
Str 3 delay shot 2 0...300000 ms 10 0 Delay time for start3 2nd reclose
Str 3 delay shot 3 0...300000 ms 10 0 Delay time for start3 3rd reclose
Str 3 delay shot 4 0...300000 ms 10 0 Delay time for start3, 4th reclose
Str 4 delay shot 1 0...300000 ms 10 0 Delay time for start4, 1st reclose
Str 4 delay shot 2 0...300000 ms 10 0 Delay time for start4 2nd reclose
Str 4 delay shot 3 0...300000 ms 10 0 Delay time for start4 3rd reclose
Str 4 delay shot 4 0...300000 ms 10 0 Delay time for start4, 4th reclose
9.4.9 Monitored data
Table 671: DARREC Monitored data
Name
Type Values (Range) Unit Description
DISA_COUNT BOOLEAN 0=False
1=True
Signal for counter
disabling
FRQ_OPR_CNT INT32 0...2147483647 Frequent operation
counter
FRQ_OPR_AL BOOLEAN 0=False
1=True
Frequent operation
counter alarm
Table continues on next page
1MRS758755 A Section 9
Control functions
REC615 and RER615 663
Technical Manual