3.14.5.3 Signals
Table 56: GOOSERCV_INTL Output signals
Name
Type Description
POS_OP BOOLEAN Position open output signal
POS_CL BOOLEAN Position closed output signal
POS_OK BOOLEAN Position OK output signal
VALID BOOLEAN Output signal
3.14.6 GOOSERCV_CMV function block
3.14.6.1 Function block
GUID-4C3F3A1A-F5D1-42E1-840F-6106C58CB380 V1 EN
Figure 53: Function block
3.14.6.2 Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs
to the application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined
in the GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application.
Default value (0) is used if VALID output indicates invalid status.
3.14.6.3 Signals
Table 57: GOOSERCV_CMV Output signals
Name
Type Description
MAG FLOAT32 Output signal (amplitude)
ANG FLOAT32 Output signal (angle)
VALID BOOLEAN Output signal
Section 3 1MRS758755 A
Basic functions
110 REC615 and RER615
Technical Manual