When the Operation mode is set to "Pulsed", the corresponding output can be used to
produce the predefined length of pulses. Once activated, the output remains active for
the duration of the set pulse length. When activated, the additional activation
command does not extend the length of pulse. Thus, the pulse needs to be ended before
the new activation can occur.
The Description setting can be used for storing signal names for each output.
Each control point or SPCLGAPC can only be accessed through the LHMI control.
SPCLGAPC follows the local or remote (L/R) state if the Loc Rem restriction setting
is "true". If the Loc Rem restriction setting is "false", local or remote (L/R) state is
ignored, that is, all controls are allowed regardless of the local or remote state.
The BLOCK input can be used for blocking the output functionality. The BLOCK input
operation depends on the Operation mode setting. If the Operation mode setting is set
to "Toggle", the output state cannot be changed when the input BLOCK is TRUE. If the
Operation mode setting is set to "Pulsed", the activation of the BLOCK input resets the
output to the FALSE state.
3.16.14.4 Signals
Table 182: SPCLGAPC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
Table 183: SPCLGAPC Output signals
Name
Type Description
O1 BOOLEAN Output 1 status
O2 BOOLEAN Output 2 status
O3 BOOLEAN Output 3 status
O4 BOOLEAN Output 4 status
O5 BOOLEAN Output 5 status
O6 BOOLEAN Output 6 status
O7 BOOLEAN Output 7 status
O8 BOOLEAN Output 8 status
O9 BOOLEAN Output 9 status
O10 BOOLEAN Output 10 status
O11 BOOLEAN Output 11 status
O12 BOOLEAN Output 12 status
O13 BOOLEAN Output 13 status
O14 BOOLEAN Output 14 status
O15 BOOLEAN Output 15 status
O16 BOOLEAN Output 16 status