Table 533: TCSSCBR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 20...60000 ms 1 1000 Reset delay time
6.1.8 Monitored data
Table 534: TCSSCBR Monitored data
Name Type Values (Range) Unit Description
TCSSCBR Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.1.9 Technical revision history
Table 535: TCSSBR Technical revision history
Technical revision Change
B Internal improvement
C Internal improvement
6.2 Fuse failure supervision SEQSPVC
6.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision SEQSPVC FUSEF 60
6.2.2 Function block
GUID-1843AD62-0328-4BBF-B8D6-EF28945855D8 V1 EN
Figure 271: Function block
1MRS758755 A Section 6
Supervision functions
REC615 and RER615 519
Technical Manual