OR
TRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC1
OPERATE
NSPTOC2_OPERATE
FPHLPDOC1_OPERATE
PHHPTOC1_OPERATE
PHIPTOC1_OPERATE
FDPHLPDOC1_OPERATE
DPHHPDOC1_OPERATE
EFPADM1_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
WPWDE1_OPERATE
WPWDE2_OPERATE
FDPHLPDOC2_OPERATE
X100 PO1
PDNSPTOC1_OPERATE
WPWDE3_OPERATE
NSPTOC1_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTOV3_OPERATE
PHPTUV1_OPERATE
PHPTUV2_OPERATE
PHPTUV3_OPERATE
NSPTOV1_OPERATE
PSPTUV1_OPERATE
SPCGGIO1_SW_MODE_ENA
FEFLPTOC1_OPERATE
EFIPTOC1_OPERATE
EFHPTOC1_OPERATE
FDEFLPDEF1_OPERATE
DEFHPDEF1_OPERATE
FDEFLPDEF2_OPERATE
FRPFRQ2_OPERATE
FRPFRQ1_OPERATE
GUID-8A61B6AD-F056-4B07-8CA2-323DF23D8B94 V1 EN
Figure 247: Typical TRPPTRC connection with RER615
5.3.6 Signals
Table 507: TRPPTRC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0=False Block of function
OPERATE BOOLEAN 0=False Operate
RST_LKOUT BOOLEAN 0=False Input for resetting the circuit breaker lockout
function
Table 508: TRPPTRC Output signals
Name
Type Description
TRIP BOOLEAN General trip output signal
CL_LKOUT BOOLEAN Circuit breaker lockout output (set until reset)
Section 5 1MRS758755 A
Protection related functions
480 REC615 and RER615
Technical Manual