Warning indication Warning code Additional information
Warning
ARC2 cont. light
86 A continuous light has been detected on
the ARC light input 2.
Warning
ARC3 cont. light
87 A continuous light has been detected on
the ARC light input 3.
Warning
RTD card error,X130
96 Temporary error occurred in RTD card
located in slot X130.
Warning
RTD meas. error,X130
106 Measurement error in RTD card located in
slot X130.
For further information on warning indications, see the operation manual.
3.2 LED indication control
3.2.1 Function block
GUID-B5D22C6D-951D-4F34-BE68-F5AF08580140 V2 EN
Figure 13: Function block
3.2.2 Functionality
The protection relay includes a global conditioning function LEDPTRC that is used
with the protection indication LEDs.
LED indication control should never be used for tripping purposes.
There is a separate trip logic function TRPPTRC available in the relay
configuration.
LED indication control is preconfigured in a such way that all the protection function
general start and operate signals are combined with this function (available as output
signals OUT_START and OUT_OPERATE). These signals are always internally
connected to Start and Trip LEDs. LEDPTRC collects and combines phase
information from different protection functions (available as output signals
OUT_ST_A /_B /_C and OUT_OPR_A /_B /_C). There is also combined earth
fault information collected from all the earth-fault functions available in the relay
configuration (available as output signals OUT_ST_NEUT and OUT_OPR_NEUT).
1MRS758755 A Section 3
Basic functions
REC615 and RER615 49
Technical Manual