EasyManua.ls Logo

ABB RELION Series - Signals

ABB RELION Series
804 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2.6 Signals
Table 499: CCBRBRF Input signals
Name
Type Default Description
I_A SIGNAL 0 Phase A current
I_B SIGNAL 0 Phase B current
I_C SIGNAL 0 Phase C current
Io SIGNAL 0 Residual current
BLOCK BOOLEAN 0=False Block CBFP operation
START BOOLEAN 0=False CBFP start command
POSCLOSE BOOLEAN 0=False CB in closed position
CB_FAULT BOOLEAN 0=False CB faulty and unable to trip
Table 500: CCBRBRF Output signals
Name Type Description
CB_FAULT_AL BOOLEAN Delayed CB failure alarm
TRBU BOOLEAN Backup trip
TRRET BOOLEAN Retrip
5.2.7 Settings
Table 501: CCBRBRF Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Current value 0.05...2.00 xIn 0.01 0.30 Operating phase current
Current value Res 0.05...2.00 xIn 0.01 0.30 Operating residual current
CB failure trip mode 1=2 out of 4
2=1 out of 3
3=1 out of 4
2=1 out of 3 Backup trip current check mode
CB failure mode 1=Current
2=Breaker status
3=Both
1=Current Operating mode of function
CB fail retrip mode 1=Off
2=Without Check
3=Current check
1=Off Operating mode of retrip logic
Retrip time 0...60000 ms 10 120 Delay timer for retrip
CB failure delay 0...60000 ms 10 240 Delay timer for backup trip
Section 5 1MRS758755 A
Protection related functions
474 REC615 and RER615
Technical Manual

Table of Contents

Other manuals for ABB RELION Series

Related product manuals