5.3.7 Settings
Table 509: TRPPTRC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Trip pulse time 20...60000 ms 1 250 Minimum duration of trip output signal
Trip output mode 1=Non-latched
2=Latched
3=Lockout
1=Non-latched Select the operation mode for trip output
5.3.8 Monitored data
Table 510: TRPPTRC Monitored data
Name Type Values (Range) Unit Description
TRPPTRC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.3.9 Technical revision history
Table 511: TRPPTRC Technical revision history
Technical revision
Change
B -
C -
D Internal improvement.
E Setting
Trip output mode
default setting is
changed to "Latched".
F Internal improvement.
5.4 Fault locator SCEFRFLO
5.4.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fault locator SCEFRFLO FLOC 21FL
1MRS758755 A Section 5
Protection related functions
REC615 and RER615 481
Technical Manual