7.1.7 Settings
Table 558: SSCBR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Acc stop current 5.00...500.00 A 0.01 10.00 RMS current setting below which engy
acm stops
Open alarm time 0...200 ms 1 40 Alarm level setting for open travel time in
ms
Close alarm time 0...200 ms 1 40 Alarm level Setting for close travel time in
ms
Spring charge time 0...60000 ms 10 15000 Setting of alarm for spring charging time of
CB in ms
Alarm Op number 0...99999 1 200 Alarm limit for number of operations
Lockout Op number 0...99999 1 300 Lock out limit for number of operations
Current exponent 0.00...2.00 0.01 2.00 Current exponent setting for energy
calculation
Difference Cor time -10...10 ms 1 5 Corr. factor for time dif in aux. and main
contacts open time
Alm Acc currents Pwr 0.00...20000.00 0.01 2500.00 Setting of alarm level for accumulated
currents power
LO Acc currents Pwr 0.00...20000.00 0.01 2500.00 Lockout limit setting for accumulated
currents power
Directional Coef -3.00...-0.50 0.01 -1.50 Directional coefficient for CB life
calculation
Initial CB Rmn life 0...99999 1 5000 Initial value for the CB remaining life
Rated Op current 100.00...5000.00 A 0.01 1000.00 Rated operating current of the breaker
Rated fault current 500.00...75000.00 A 0.01 5000.00 Rated fault current of the breaker
Op number rated 1...99999 1 10000 Number of operations possible at rated
current
Op number fault 1...10000 1 1000 Number of operations possible at rated
fault current
Inactive Alm days 0...9999 1 2000 Alarm limit value of the inactive days
counter
Travel time Clc mode 1=From Cmd to
Pos
2=From Pos to Pos
2=From Pos to Pos Travel time calculation mode selection
Table 559: SSCBR Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Opening time Cor -100...100 ms 1 10 Correction factor for open travel time in ms
Closing time Cor -100...100 ms 1 10 Correction factor for CB close travel time
in ms
Counter initial Val 0...99999 1 0 The operation numbers counter
initialization value
Ini Acc currents Pwr 0.00...20000.00 0.01 0.00 Initial value for accumulation energy (Iyt)
Table continues on next page
Section 7 1MRS758755 A
Condition monitoring functions
550 REC615 and RER615
Technical Manual