Parameter Values (Range) Unit Step Default Description
Min operate current 0.01...1.00 xIn 0.01 0.01 Minimum operating current
Min operate voltage 0.01...1.00 xUn 0.01 0.01 Minimum operating voltage
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used Io signal
Uo signal Sel 1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used Uo signal
4.2.4.9 Monitored data
Table 366: EFPADM Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
COND_RES FLOAT32 -1000.00...1000.
00
mS Real part of calculated
neutral admittance
SUS_RES FLOAT32 -1000.00...1000.
00
mS Imaginary part of
calculated neutral
admittance
EFPADM
Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.4.10 Technical data
Table 367: EFPADM Technical data
Characteristic
Value
Operation accuracy
1)
At the frequency f = f
n
±1.0% or ±0.01 mS
(In range of 0.5...100 mS)
Start time
2)
Minimum Typical Maximum
56 ms 60 ms 64 ms
Reset time 40 ms
Operate time accuracy ±1.0% of the set value of ±20 ms
Suppression of harmonics -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) Uo = 1.0 × Un
2) Includes the delay of the signal output contact, results based on statistical distribution of 1000
measurements
Section 4 1MRS758755 A
Protection functions
352 REC615 and RER615
Technical Manual