4.7.7 Settings
Table 486: MAPGAPC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value -10000.0...10000.0 0.1 0.0 Start value
Start value Add -100.0...100.0 0.1 0.0 Start value Add
Operate delay time 0...200000 ms 100 0 Operate delay time
Table 487: MAPGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Operation mode 1=Over
2=Under
1=Over Operation mode
Table 488: MAPGAPC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 100 0 Reset delay time
Absolute hysteresis 0.01...100.00 0.01 0.10 Absolute hysteresis for operation
4.7.8 Monitored data
Table 489: MAPGAPC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
MAPGAPC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.7.9 Technical data
Table 490: MAPGAPC Technical data
Characteristic
Value
Operation accuracy ±1.0% of the set value or ±20 ms
Section 4 1MRS758755 A
Protection functions
460 REC615 and RER615
Technical Manual