8.1.11.7 Technical revision history
Table 615: PEMMXU Technical revision history
Technical revision
Change
B Demand values added to Monitored data.
Recorded data added to store minimum and
maximum demand values with timestamps.
C
Internal improvement.
D Internal improvement.
8.1.12 Single-phase power and energy measurement SPEMMXU
8.1.12.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single-phase power and energy
measurement
SPEMMXU SP, SE SP, SE
8.1.12.2 Function block
Figure 303: Function block
8.1.12.3 Signals
Table 616: SPEMMXU Input signals
Name
Type Default Description
RSTACM BOOLEAN 0=False Reset of accumulated energy reading
8.1.12.4 Settings
Table 617: SPEMMXU Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Power unit Mult 3=k
6=M
3=k Unit multiplier for presentation of the
power related values
Energy unit Mult 3=k
6=M
3=k Unit multiplier for presentation of the
energy related values
Active power Dir 1=Forward
2=Reverse
1=Forward Direction of active power flow: forward,
reverse
Reactive power Dir 1=Forward
2=Reverse
1=Forward Direction of reactive power flow: forward,
reverse
1MRS758755 A Section 8
Measurement functions
REC615 and RER615 585
Technical Manual