Table 293: EFHPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
Table 294: EFIPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.2.1.9 Settings
Table 295: FEFLPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.010...5.000 xIn 0.005 0.010 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scaling the start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier in IEC/ANSI IDMT curves
Table continues on next page
Section 4 1MRS758755 A
Protection functions
270 REC615 and RER615