Section 14 Technical data
Table 731: Dimensions
Description Value
Width Frame 177 mm
Case 164 mm
Height Frame 177 mm (4U)
Case 160 mm
Depth 201 mm (153 + 48 mm)
Weight Complete protection relay 4.1 kg
Plug-in unit only 2.1 kg
Table 732: Power supply
Description Type 1 Type 2
Nominal auxiliary voltage U
n
100, 110, 120, 220, 240 V AC,
50 and 60 Hz
24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in
the auxiliary DC voltage without
resetting the relay
50 ms at U
n
Auxiliary voltage variation 38...110% of U
n
(38...264 V AC) 50...120% of U
n
(12...72 V DC)
80...120% of U
n
(38.4...300 V
DC)
Start-up threshold 19.2 V DC (24 V DC × 80%)
Burden of auxiliary voltage
supply under quiescent (P
q
)/
operating condition
DC <13.0 W (nominal)/<18.0 W
(max.)
AC <16.0 W (nominal)/<21.0 W
(max.)
DC <13.0 W (nominal)/<18.0 W
(max.)
Ripple in the DC auxiliary
voltage
Max 15% of the DC value (at frequency of 100 Hz)
Fuse type T4A/250 V
The protection relay does not include any batteries as backup power
when the auxiliary power goes down. However, the relay
configuration and settings, events, disturbance recordings and any
critical data stay in the relay's memory because those are saved to a
nonvolatile memory. Also, the relay's real-time clock is kept running
via a 48-hour capacitor backup.