Table 228: PHIPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.1.1.10 Monitored data
Table 229: FPHLPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
FPHLPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 230: PHLPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
PHLPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 231: PHHPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
PHHPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 232: PHIPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
PHIPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 A Section 4
Protection functions
REC615 and RER615 221
Technical Manual