4.1.1.11 Technical data
Table 233: (F)PHxPTOC Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the measured
current: f
n
±2 Hz
(F)PHLPTOC
±1.5% of the set value or ±0.002 × I
n
PHHPTOC
and
PHIPTOC
±1.5% of set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Start time
1)2)
Minimum Typical Maximum
PHIPTOC:
I
Fault
= 2 × set
Start
value
I
Fault
= 10 × set
Start
value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
PHHPTOC and
(F)PHLPTOC:
I
Fault
= 2 × set
Start
value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio Typically 0.96
Retardation time <30 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
±5.0% of the theoretical value or ±40 ms
3)4)
Suppression of harmonics RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
Measurement mode
= default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 50 Hz, fault current
in one phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value
= 2.5 × I
n
,
Start value
multiples in range of 1.5...20
4) Valid for FPHLPTOC
4.1.1.12 Technical revision history
Table 234: PHIPTOC Technical revision history
Technical revision
Change
B Minimum and default values changed to 40 ms for
the
Operate delay time
setting
C Minimum and default values changed to 20 ms for
the
Operate delay time
setting
Minimum value changed to 1.00 x I
n
for the
Start
value
setting
D
Internal improvement
E Internal improvement
Section 4 1MRS758755 A
Protection functions
222 REC615 and RER615
Technical Manual