5.1.6 Signals
Table 491: INRPHAR Input signals
Name
Type Default Description
I_2H_A SIGNAL 0 Second harmonic phase A current
I_1H_A SIGNAL 0 Fundamental frequency phase A current
I_2H_B SIGNAL 0 Second harmonic phase B current
I_1H_B SIGNAL 0 Fundamental frequency phase B current
I_2H_C SIGNAL 0 Second harmonic phase C current
I_1H_C SIGNAL 0 Fundamental frequency phase C current
BLOCK BOOLEAN 0=False Block input status
Table 492: INRPHAR Output signals
Name Type Description
BLK2H BOOLEAN Second harmonic based block
5.1.7 Settings
Table 493: INRPHAR Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 5...100 % 1 20 Ratio of the 2. to the 1. harmonic leading
to restraint
Operate delay time 20...60000 ms 1 20 Operate delay time
Table 494: INRPHAR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Table 495: INRPHAR Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
5.1.8 Monitored data
Table 496: INRPHAR Monitored data
Name
Type Values (Range) Unit Description
INRPHAR Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 5 1MRS758755 A
Protection related functions
464 REC615 and RER615
Technical Manual