3.13.3.4 Signals
Table 46: ULTVTR Input signals
Name
Type Default Description
UL1 INT32-UL1 0 IEC61850-9-2 phase 1 voltage
UL2 INT32-UL2 0 IEC61850-9-2 phase 2 voltage
UL3 INT32-UL3 0 IEC61850-9-2 phase 3 voltage
MINCB_OPEN BOOLEAN 0=False Active when external MCB opens protected voltage
circuit
Table 47: ULTVTR Output signals
Name Type Description
ALARM BOOLEAN Alarm
WARNING BOOLEAN Warning
3.13.3.5 Settings
Table 48: ULTVTR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Primary voltage 0.100...440.000 kV 0.001 20.000 Primary rated voltage
Secondary voltage 60...210 V 1 100 Secondary rated voltage
VT connection 1=Wye
2=Delta
3=U12
4=UL1
2=Delta Voltage transducer measurement
connection
Amplitude Corr A 0.9000...1.1000 0.0001 1.0000 Phase A Voltage phasor magnitude
correction of an external voltage
transformer
Amplitude Corr B
0.9000...1.1000 0.0001 1.0000 Phase B Voltage phasor magnitude
correction of an external voltage
transformer
Amplitude Corr C
0.9000...1.1000 0.0001 1.0000 Phase C Voltage phasor magnitude
correction of an external voltage
transformer
Division ratio
1000...20000 1 10000 Voltage sensor division ratio
Voltage input type 1=Voltage trafo
3=CVD sensor
1=Voltage trafo Type of the voltage input
Angle Corr A -20.0000...20.0000 deg 0.0001 0.0000 Phase A Voltage phasor angle correction
of an external voltage transformer
Angle Corr B -20.0000...20.0000 deg 0.0001 0.0000 Phase B Voltage phasor angle correction
of an external voltage transformer
Angle Corr C -20.0000...20.0000 deg 0.0001 0.0000 Phase C Voltage phasor angle correction
of an external voltage transformer
Section 3 1MRS758755 A
Basic functions
104 REC615 and RER615
Technical Manual