8.1.11.3 Signals
Table 610: PEMMXU Input signals
Name
Type Default Description
RSTACM BOOLEAN 0=False Reset of accumulated energy reading
8.1.11.4 Settings
Table 611: PEMMXU Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Power unit Mult 3=Kilo
6=Mega
3=Kilo Unit multiplier for presentation of the
power related values
Energy unit Mult 3=Kilo
6=Mega
3=Kilo Unit multiplier for presentation of the
energy related values
Active power Dir 1=Forward
2=Reverse
1=Forward Direction of active power flow: Forward,
Reverse
Reactive power Dir 1=Forward
2=Reverse
1=Forward Direction of reactive power flow: Forward,
Reverse
Table 612: PEMMXU Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Forward Wh Initial 0...999999999 1 0 Preset Initial value for forward active
energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value for reverse active
energy
Forward VArh Initial 0...999999999 1 0 Preset Initial value for forward reactive
energy
Reverse VArh Initial 0...999999999 1 0 Preset Initial value for reverse reactive
energy
Measurement mode 1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
1=PhsA, PhsB,
PhsC
Selected measurement mode for power
calculation
Section 8 1MRS758755 A
Measurement functions
582 REC615 and RER615
Technical Manual