Loading...
GOOSERCV_ENUM function block does not receive the value from the sending
device or it is invalid, the default value (0) is used and the ALARM is activated in the
T_HEALTH function block.
3.15.4.3 Signals
Table 66: T_HEALTH Input signals
Name Type Default Description
IN1 Any 0 Input signal
Table 67: T_HEALTH Output signals
Name Type Description
OK BOOLEAN Output signal
WARNING BOOLEAN Output signal
ALARM BOOLEAN Output signal
3.15.5 T_F32_INT8 function block
3.15.5.1 Function block
GUID-F0F44FBF-FB56-4BC2-B421-F1A7924E6B8C V1 EN
Figure 60: Function block
3.15.5.2 Functionality
The T_F32_INT8 function is used to convert 32-bit floating type values to 8-bit
integer type. The rounding operation is included. Output value saturates if the input
value is below the minimum or above the maximum value. .
3.15.5.3 Signals
Table 68: T_F32_INT8 Input signals
Name
Type Default Description
F32 FLOAT32 0.0 Input signal
Table 69: T_F32_INT8 Output signal
Name
Type Description
INT8 INT8 Output signal