Name Type Values (Range) Unit Description
MAN_CB_CL BOOLEAN 0=False
1=True
Indicates CB manual
closing during reclosing
sequence
SOTF
BOOLEAN 0=False
1=True
Switch-onto-fault
DARREC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.4.10 Technical data
Table 672: DARREC Technical data
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
9.4.11 Technical revision history
Table 673: DARREC Technical revision history
Technical revision
Change
B The PROT_DISA output removed and removed
the related settings
C The default value of the
CB closed Pos status
setting changed from "True" to "False"
D SHOT_PTR output range 0...7 (earlier 0...6)
E Monitored data ACTIVE transferred to be ACT
visible output. SHOT_PTR output range 1...7.
F Internal improvement
9.5 Automatic transfer switch ATSABTC
9.5.1 Identification
Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Automatic transfer switch
ATSABTC ATSABTC ATSABTC
1MRS758755 A Section 9
Control functions
REC615 and RER615 665
Technical Manual