Parameter Values (Range) Unit Step Default Description
Time multiplier 0.05...2.00 0.01 1.00 Time multiplier for Wattmetric IDMT
curves
Operating curve type 5=ANSI Def. Time
15=IEC Def. Time
20=Wattmetric
IDMT
15=IEC Def. Time Selection of time delay curve type
Operate delay time 60...200000 ms 10 60 Operate delay time for definite time
Table 381: WPWDE Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Table 382: WPWDE Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used current measurement mode
Correction angle 0.0...10.0 deg 0.1 2.0 Angle correction
Min operate current 0.010...1.000 xIn 0.001 0.010 Minimum operating current
Min operate voltage 0.01...1.00 xUn 0.01 0.01 Minimum operating voltage
Reset delay time 0...60000 ms 1 20 Reset delay time
Pol reversal 0=False
1=True
0=False Rotate polarizing quantity
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used Io signal
Uo signal Sel 1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used polarization signal
4.2.6.10 Monitored data
Table 383: WPWDE Monitored data
Name
Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE FLOAT32 -180.00...180.00 deg Angle between polarizing
and operating quantity
Table continues on next page